Produktinfo

APC Symmetra PX 64kW Scalable to 160kW, 400V

Modular, high-efficiency 3-phase UPS that is scalable as your data center grows up to 160kW/160kVA. Suitable for small, medium & large data center applications.

Includes: Network Management Card, Start-Up Service, User Manual

General

Bypass Connection
5 wire (3PH + N + G)
Max Bypass Input Current
250A
Bypass Protection Device
250A
Output

Output Power Capacity
64 kW / 64 kVA
Max Configurable Power
160 kW / 160 kVA
Nominal Output Voltage
230V,400V 3PH
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load
95%
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor
Unlimited
Waveform Type
Sine wave
Output Connections
(1) Hard Wire 5-wire (3PH + N + G)
Output Voltage Tolerance
+/-1% static and +/- 5% at 100% load step
Output Voltage THD
< 2% for 0 to 100% linear load and < 6% for full n
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load
95%
Required Output Current Protection
250A
Neutral Output Current
160A
Bypass
Built-in Static Bypass
Input

Nominal Input Voltage
400V 3PH
Input Frequency
40 - 70 Hz
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations
340 - 477V
Input voltage adjustable range for mains operation
340 - 460 (400V)V
Maximum Input Current
132A
Input Breaker Capacity
315.0  A
Input Total Harmonic Distortion
Less than 5% for full load
Batteries & Runtime

Battery Type VRLA
Included Battery Modules 6
Available Battery Slots 3
Typical recharge time 3.50 hour(s)
RBC™ Quantity 4
Nominal Battery Voltage +/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage +/-154 V
DC Overcurrent Protection 320A
Maximum Available Short Circuit Current 4 kA
Efficiency in Battery Operation 94%
End of Discharge Maximum Battery Current 221
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Communications & Management

Interface Port(s)
SmartSlot
Control panel
Multi-function LCD status and control console
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO)
Yes
Physical

Maximum Height
1991.00 mm
Maximum Width
1200.00 mm
Maximum Depth
1070.00 mm
Rack Height
42U
Net Weight
1388.00 KG
Shipping Weight
1511.00 KG
Shipping Height
2140.00 mm
Shipping Width
1696.00 mm
Shipping Depth
1210.00 mm
Color
Black
Environmental

Operating Environment
0 - 40 °C
Operating Relative Humidity
0 - 95%
Operating Elevation
0-999.9 meters
Storage Temperature
-15 - 40 °C
Storage Relative Humidity
0 - 95%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from surface of unit
63.00 dBA
Online Thermal Dissipation
11496.00 BTU/hr
Protection Class
NEMA 1
Conformance

Regulatory Approvals
EN 50091-1,EN/IEC 62040-3,EN/IEC 62040-1-1,FCC Part 15 Class A,VFI-SS-111
Standard Warranty
1 year on-site repair or replace with factory authorized Start-Up